All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation GS 05D01D12-02E 4th Edition Mar. 01, 2005-00
Hardware Specifications
PV Input Signal
Number of input points: 1
Input system:
The type of input and instrument range can be
specified using the table of PV input shown
below by key operation or communication.
Sampling period: 250 ms
Input type, instrument range and measurement accuracy:
Refer to the table below.
-200 to 1370C
-199.9 to 999.9C
-199.9 to 500.0C
-199.9 to 999.9C
-199.9 to 400.0C
0.0 to 400.0C
0 to 1800C
0 to 1700C
0 to 1700C
-200 to 1300C
-199.9 to 999.9C
-199.9 to 900.0C
-199.9 to 400.0C
0.0 to 400.0C
0 to 2300C
0 to 1390C
0 to 1900C
0 to 2000C
-199.9 to 500.0C
-150.0 to 150.0C
-199.9 to 850.0C
-199.9 to 500.0C
-150.0 to 150.0C
-300 to 2500F
0 to 2300F
-199.9 to 999.9F
-300 to 2300F
-300 to 750F
-199.9 to 750.0F
32 to 3300F
32 to 3100F
32 to 3100F
-300 to 2400F
-300 to 1800F
-300 to 1300F
-300 to 750F
-199.9 to 750.0F
32 to 4200F
32 to 2500F
32 to 3400F
32 to 3600F
-199.9 to 999.9F
-199.9 to 300.0F
-300 to 1560F
-199.9 to 999.9F
-199.9 to 300.0F
Thermocouple
RTD
Standard
signal
DC voltage
K
J
T
B
S
R
N
E
L (DIN)
U (DIN)
W (DIN)
Platinel 2
PR20-40
W97Re3-W75Re25
JPt100
Pt100
0.4 to 2 V
1 to 5 V
0 to 2 V
0 to 10 V
-10 to 20 mV
0 to 100 mV
0.1% of instrument range 1 digit for
temperatures equal to or higher than 0 C,
0.2% of instrument range 1 digit for
temperatures below 0 C
0.15% of instrument range 1 digit for
temperatures equal to or higher than 400 C
5% of instrument range 1 digit for
temperatures below 400 C
0.15% of instrument range 1 digit
0.1% of instrument range 1 digit
0.25% of instrument range 1 digit for
temperature below 0 C
0.1% of instrument range 1 digit for
temperatures equal to or higher than 0 C
0.2% of instrument range 1 digit for
temperatures below 0 C
0.2% of instrument range 1 digit
0.1% of instrument range 1 digit
0.5% of instrument range 1 digit for
temperatures equal to or higher than 800 C
No guarantee of accuracy for temperatures
below 800 C
0.2% of instrument range 1 digit
0.1% of instrument range 1 digit (Note 1)
(Note 2)
0.2% of instrument range 1 digit (Note 1)
0.1% of instrument range 1 digit (Note 1)
(Note 2)
0.2% of instrument range 1 digit (Note 1)
0.1% of instrument range 1 digit
The read-out range can be scaled between -
1999 and 9999.
Input type Instrument range (˚C)
Instrument range (˚F)
Measurement accuracy
*1
Input range
code
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
30
31
35
36
37
40
41
50
51
55
56
0.400 to 2.000
1.000 to 5.000
0.000 to 2.000
0.00 to10.00
-10.00 to 20.00
0.0 to 100.0
Scaling is enable in the following
4 range.
-1999 to 9999
-199.9 to 999.9
-19.99 to 99.99
-1.999 to 9.999
Unspecified(when shipped from the factry)
OFF Set the data item PV input Type"IN" to the OFF option to leave the PV input type undefined.
Note 1: The accuracy is 0.3C of instrument range 1 digit for a temperature range from 0 to 100C.
Note 2: The accuracy is 0.5C of instrument range 1 digit for a temperature range from -100 to 0C and 100 to 200C.
*1: Performance in the standard operating conditon (at 23C 2C, 5510%RH, and 50/60Hz power frequency)
*2: To receive a 4 to 20 mA DC signal, select a Standard signal of 1 to 5 V DC and connect it to a 250 resistor.
This resistor is optional Model: X010-250-2 (resistor with M3.5 crimp-on-terminal lugs)
Burnout detection:
Functions at thermocouple (TC), RTD or
standard signal of 0.4 to 2 V or 1 to 5 V.
Upscale, downscale, and off can be specified.
For standard signal, set to burnout at 0.1 V or
less.
Input bias current: 0.05 µA for TC and RTD b-terminal
Measurement current(RTD): About 0.13 mA
Input resistance:
1 M or more for TC or mV input
About 1 M for DC voltage input
Allowable signal source resistance:
250 or less for TC or mV input
Effects of signal source resistance:
0.1 µV/ or less
2 k or less for DC voltage input
Effects of signal source resistance:
About 0.01%/100