GS 05D01D12-02E 4th Edition Mar. 01, 2005-00
Allowable wiring resistance:
Max. 150 Ω/wire (resistance in each of three
wires must be equal) for RTD input
However, max. 10 Ω/wire for the range of
–150.0 to 150.0°C.
Wiring resistance effect: ±0.1°C/10 Ω
Allowable input voltage:
±10 V DC for TC, mV or RTD input
±20 V DC for DC voltage input
Noise rejection ratio:
Normal mode 40 dB (50/60 Hz) or more
Common mode 120 dB (50/60 Hz) or more
Reference junction compensation error:
±1.0°C (15 to 35°C),
±1.5°C (0 to 15°C, 35 to 50°C)
Applicable standards:
JIS, IEC, or DIN (ITS-90) for TC and RTD
24 V DC Loop Power Supply for Sensor
Supplies power to a two-wire transmitter.
A resistor (10 to 250Ω) connected between the controller and
the transmitter converts a current signal into a voltage signal,
which is then read by the PV input terminal.
Supply voltage: 21.6 to 28.0 V DC
Maximum supply current : 30 mA (only for models with
24 V DC loop power supply)
Ambient temperature should be 0 to 40°C when using 24
V DC loop power supply for UT321.
12
13
21
22
Two-wire transmitter
Loop power
supply
21.6 to
28.0 V DC
PV input
1 to 5 V DC signal
External
resistor
(Note)
4-20 mADC
■ 24 V DC Power Supply Wiring to Two-wire Sensor
250Ω
Note: Connecting a 250
Ω
resistor to the terminals is optional.
Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
Retransmission Output
Any of PV, target setpoint, or control output is output. Can
also be used for 15 V DC loop power supply.
Number of output points: 1
Output signal: 4 to 20 mA DC
Load resistance: 600 Ω or less
Output accuracy: ±0.3% of span
Performance in the standard operating
conditions (at 23± 2°C, 55± 10% RH, and 50/
60 Hz power frequency)
When used for 15 V DC loop power supply:
Supply voltage: 14.5 to 18.0 V DC
Maximum supply current : About 21 mA
(with the protection circuit at field short
circuit).
Control Outputs
The control output is of a universal scheme and can be
selected from the following types of outputs. In the case of
heating/cooling control, it is also selectable from these
outputs. However, if the cooling-side output is a relay
contact output, the alarm-3 cannot be used, and similarly if
the cooling-side output is a voltage pulse or current output,
the retransmission output (15 V DC loop power supply)
cannot be used.
Current output
Number of output points:
1 or 2 (2 for heating/cooling type)
Selected between voltage pulse output.
Output signal: 4 to 20 mA DC
Load resistance: 600 Ω or less
Output accuracy: ±0.3% of span
Performance in the standard operating
conditions (at 23± 2°C, 55± 10% RH, and
50/60 Hz power frequency)
Voltage pulse output
Number of output points:
1 or 2 (2 for heating/cooling type)
Selected between current output.
Output signal:
On voltage = 12 V DC or more (load
resistance; 600 Ω or more, current at short-
circuit; about 30 mA)
Off voltage = 0.1 V DC or less
Resolution: 10 ms
Relay contact output
Number of output points:
1 or 2 (2 for heating/cooling type)
Output signal:
At three terminals of NC, NO and Common,
transfer-contact
Contact rating:
250 V AC, 3 A or 30 V DC, 3 A (resistive
load)
Resolution: 10 ms
Contact Inputs
Usage: Target setpoint selection, Auto/Man mode
switching, or Key lock parameter show/hide
switching
Number of input points: 2
Input type: Non-voltage contact input or transistor open
collector input
Input contact rating:
12 V DC, 10 mA or more (for non-voltage
contact input)
On/off detection:
For non-voltage contact input,
ON= contact resistance; 1 kΩ or less,
OFF= contact resistance; 20 kΩ or more.
For transistor open collector input,
ON= 2 V or less,
OFF= leakage current; 100 µA or less.
Minimum retention time for status detection:
About 1 s
Contact Outputs
Usage: Alarm output, FAIL output, and others
Number of relay contact output points: 3
Relay contact rating:
240 V AC, 1 A or 30 V DC, 1 A
a-contact (COM terminals are common for
every contact output.) (b-contact for FAIL
output)
● Display Unit Specifications
PV display: 4-digit, 7-segment green/red LED; each digit
12 mm in height
Setpoint display:
4-digit, 7-segment red LED; each digit 9.3
mm in height
Status indicator lamps: LEDs