General
Specifications
<<Contents>> <<Index>>
GS 05D01D12-02E
GS 05D01D12-02E
©Copyright Apr. 2003
4th Edition Mar. 2005
UT321
UT321E
“E” indicates the
model with expanded
functions.
Indication
in green or
red color
Model UT321
Digital Indicating Controller
with Active Color PV Display
General
Model UT321 Digital Indicating Controller is a precision 1/8
DIN controller, provided with the PV display color changing
function "Active Color PV Display." It has a large display
for readings, universal input/output and excellent monitoring
operability with the Auto/Man switching key. In addition,
auto tuning, the overshoot suppressing function “SUPER”,
the hunting suppressing function “SUPER2” and heating/
cooling control are available as control functions, and a re-
transmission output and 15 V DC loop power supply are also
equipped as standard. A communication function or 24 V DC
loop power supply is available optionally. As described
above, the UT321 is a controller provided with higher func-
tions and capability.
Main Features
• Extra-large digital dispaly allows the indicated values to be
read even from a long distance. LEDs of 12 mm height are
used for the PV display.
• The PV display color changing function "Active Color PV
Display" is provided. PV display color is changed from green
to red and vice versa when an alarm occurs or deviation
becomes large. The color also can be fixed in green or red.
Universal input and output allow simple setting of the input
type (thermocouple, RTD or mV), PV input range, and type
of control output (4 to 20 mA current, voltage pulse, or relay
contact) from the front panel.
• Parameters can easily be set using a personal computer.
("Parameter setting tool (model LL100)" sold separately is
required.)
Various communication functions are provided. Communi-
cation is possible with personal computer, programmable
logic controller, and other controllers.
Functional Specifications
Control Computation Functions
Control computation:
Can be selected from the following types:
Continuous PID control, Time-proportional PID
control, Heating/Cooling control (for heating/
cooling type only) or Relay ON/OFF control.
Control cycle time: 250 ms
Number of sets of target setpoints and PID parameters: 4
Target setpoint and PID selection:
PID parameters are provided for every target
setpoint and the set of PID parameters are
selected at the same time that the setpoint
number is selected.
Zone PID selection:
PID parameters are selected depending on the
value of the PV. For selection, the reference
point (PID parameter selection setpoint) or the
reference deviation is used.
Reference point method:
The PV input range is divided into a
maximum of three zones with up to two
reference points, and PID parameters are
selected (No. 1 PID to No. 3 PID) for every
zone.
Reference point = PV input range (0%)
Reference point 1 Reference point 2
PV input range (100%)
Reference point hysteresis = Fixed to 0.5% of the
PV input range span.
Reference deviation method:
PID parameters (No. 4 PID) are selected
when the deviation exceeds the reference
deviation. This methods takes precedence
over the reference point method.
Reference deviation = OFF or 0.1 to 100.0% of PV
input range span
No.1PID
No.2PID
No.3PID
Reference point 1
Reference point 2
PV input range (100%)
PV input range (0%)
Measured value (PV)
Reference deviation
Reference deviation
Auto-tuning:
Available as standard. If auto-tuning is
operated, PID constants are automatically set
(limit cycle method).
“SUPER” function:
Overshoots generated by abrupt changes in the
target setpoint or by disturbances can be
suppressed.
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - Specifications

GeneralSpecifications<<Contents>> <<Index>>GS 05D01D12-02EGS 05D01D12-02E©Copyright Apr. 20034th Edition Mar. 2005UT321UT321E

Seite 2 - ● Alarm Functions

10All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation<<Contents>> <<Index>>GS 05D01D12-02E 4th Edition Mar.

Seite 3

11<<Contents>> <<Index>>All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation GS 05D01D12-02E 4th Edition Mar.

Seite 4

12All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation<<Contents>> <<Index>>GS 05D01D12-02E 4th Edition Mar.

Seite 5 - ■ Hardware Specifications

2All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation<<Contents>> <<Index>>GS 05D01D12-02E 4th Edition Mar. 0

Seite 6

3<<Contents>> <<Index>>All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation GS 05D01D12-02E 4th Edition Mar.

Seite 7 - ● Environmental Conditions

4All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation<<Contents>> <<Index>>GS 05D01D12-02E 4th Edition Mar. 0

Seite 8

5<<Contents>> <<Index>>All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation GS 05D01D12-02E 4th Edition Mar.

Seite 9

6All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation<<Contents>> <<Index>>GS 05D01D12-02E 4th Edition Mar. 0

Seite 10 - Receiving 4-20 mA DC Current

7<<Contents>> <<Index>>All Rights Reserved. Copyright © 2003, Yokogawa Electric Corporation GS 05D01D12-02E 4th Edition Mar.